Find Your LayerZero Representative
Career Opportunities at LayerZero

Product Overview

The LayerZero eRDP-FS (eRDP-1) is a web-enabled remote distribution panel (eRDP) with subfeed distribution. It is a MIMO configuration (multiple inputs, multiple outputs), meaning that it can have multiple input power sources and multiple output circuits. The eRDP is ideal for applications that require high-reliability power distribution in a space-saving design.

The core functionality of the LayerZero eRDP is to distribute power to a large number of circuits. It can accommodate subfeed circuit breakers, including both finger-safe and non-finger-safe breakers. This makes it ideal for applications with high power requirements, such as data centers and large industrial facilities.

The eRDP also features a number of safety features, including SafePanel® distribution, dead front doors, no exposed live parts (NELP) and polycarbonate windows. These features help to protect users and equipment from electrical hazards.

If you are looking for a high-reliability, safe, and versatile power distribution solution, the LayerZero eRDP is a great option.

Documents and Downloads

A one line diagram is a symbolic representation of three-phase electric power systems, depicting the paths for power flow between entities of the power distribution system.

Download
One Line

A product outline is a technical engineering drawing showing mechanical characteristics of our products.

Download
Product Outline

Product Specifications

Product Specifications

Physical Specifications

Dimensions 88" x 36" x 36" (2240 mm x 905 mm x 905 mm)
Weight 674 lbs (306 kg)
Clearances Front 36” [915mm] Rear 0 Left 1” [25mm] Right 1” [25mm] Top 18” [457mm]
Color Gray, Black
Warranty One-Year Limited Warranty
CSA Rating Certified to CSA STD C22.2#29
UL Rating Conforms to UL STD 67
Distribution Type Subfeed Distribution

System Specifications

System Input Voltage 600V, 3-Phase, 3-Wire + Ground
System Output Voltage 120/208V, 3-phase, 4-wire + Ground
System Output Voltage - 1st Alternate No
System Output Voltage - 2nd Alternate No
Transformer Size 150kVA
Secondary Neutral Rating 200%
eSTS Integration No
Input Feeder Terminations Two-hole Compression Lug Terminals
Presence of Primary Side Distribution No
Transformer Input Current Rating 144A
Transformer Output Current Rating 416A
Presence of Secondary Side Distribution Yes
Secondary Distribution Side Both
Secondary Distribution Orientation Side-facing
Distribution Type 42-pole Branch Circuit Distribution and Subfeed Breakers
Total Quantity of Branch Circuit Panel Boards 4
Total Quantity of 225A Branch Circuit SafePanels® 4
Total Quantity of 400A Branch Circuit SafePanels® 0
Exposed Live Parts or No Exposed Live Parts Exposed Live Parts (ELP)
Subfeed Circuit Breaker Type Subfeed Distribution
Secondary Subfeed Type 1200A SafePanel®
Secondary Subfeed Panel Board Quantity 1
Presence of Primary Main Circuit Breaker Yes
Presence of Primary Auxiliary Circuit Breaker No
Sync Check Relay Required N/A
Presence of Kirk Key Interlock N/A

Primary Main Circuit Breaker (CB601)

Frame Rating 250
Circuit Breaker Type Electronic Trip (LSIG)
Circuit Breaker Mounting Type Fixed
Max Steady State Rating 250
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 600VAC
Presence of Shunt Trip 24VDC
Presence of CB Position Indications Yes - wired to terminal blocks
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Transformer (T620)

Transformer size 150
Material Copper
k-Factor k-20
Efficiency Class Per DOE 2016
Temperature Rise 150
Inrush 5X Max
Nominal Impedance 5.5

Secondary Main Circuit Breaker (CB701)

Frame Rating 600
Circuit Breaker Type Electronic Trip (LSI)
Circuit Breaker Mounting Type Fixed
Max Steady State Rating 600
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Branch Circuit Panel Board 1 Main Circuit Breaker (CB821)

Frame Rating 250
Circuit Breaker Type Electronic Trip (LS/I)
Circuit Breaker Mounting Type Plug-in to SafePanel®
Max Steady State Rating 250
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Branch Circuit Panel Board 1 (PANEL 821)

Rating - Phases 225
Rating - Neutral 225
Rating - Ground 225
Withstand 22
Supplier Schneider/Square D

Branch Circuit Panel Board 2 Main Circuit Breaker (CB822)

Frame Rating 250
Circuit Breaker Type Electronic Trip (LS/I)
Circuit Breaker Mounting Type Plug-in to SafePanel®
Max Steady State Rating 250
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Branch Circuit Panel Board 2 (PANEL 822)

Rating - Phases 225
Rating - Neutral 225
Rating - Ground 225
Withstand 22
Supplier Schneider/Square D

Branch Circuit Panel Board 3 Main Circuit Breaker (CB823)

Frame Rating 250
Circuit Breaker Type Electronic Trip (LS/I)
Circuit Breaker Mounting Type Plug-in to SafePanel®
Max Steady State Rating 250
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Branch Circuit Panel Board 3 (PANEL 823)

Rating - Phases 225
Rating - Neutral 225
Rating - Ground 225
Withstand 22
Supplier Schneider/Square D

Branch Circuit Panel Board 4 Main Circuit Breaker (CB824)

Frame Rating 250
Circuit Breaker Type Electronic Trip (LS/I)
Circuit Breaker Mounting Type Plug-in to SafePanel®
Max Steady State Rating 250
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

Branch Circuit Panel Board 4 (PANEL 824)

Rating - Phases 225
Rating - Neutral 225
Rating - Ground 225
Withstand 22
Supplier Schneider/Square D

PANEL 801 Subfeed Circuit Breaker 1

Frame Rating 400
Circuit Breaker Type Electronic Trip (LS/I)
Circuit Breaker Mounting Type Plug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating 300
Percent Rating 80
Fault Rating at Rated Voltage 65kAIC @ 240VAC
Presence of Shunt Trip No
Presence of CB Position Indications Yes - monitored internally
Presence of Lockout/Tag-out Bracket Yes
Number of Poles 3
Supplier ABB

SafePanel® 1 (PANEL 801)

Current 1200
Withstand 100
Supplier ABB

Secondary Side SPD (SPD620)

Voltage 120/208
Number of Wires 4
Type Type 2 SPD
Surge Withstand 40
Presence of Alarm Indication Yes - monitored internally

CB821 Load Side Lug

Type Mechanical Lug
Cable Size (1) 10 AWG-250MCM (Cu Only)

CB822 Load Side Lug

Type Mechanical Lug
Cable Size (1) 10 AWG-250MCM (Cu Only)

CB823 Load Side Lug

Type Mechanical Lug
Cable Size (1) 10 AWG-250MCM (Cu Only)

CB824 Load Side Lug

Type Mechanical Lug
Cable Size (1) 10 AWG-250MCM (Cu Only)

N1 Neutral Lug 821-1

Type Compression Lug
Cable Size 2/0 AWG

N1 Neutral Lug 822-1

Type Compression Lug
Cable Size 2/0 AWG

N1 Neutral Lug 823-1

Type Compression Lug
Cable Size 2/0 AWG

N1 Neutral Lug 824-1

Type Compression Lug
Cable Size 2/0 AWG

IN1G-3 Lug 822-1

Type Compression Lug
Cable Size 2 AWG

G1 Lug 823-1

Type Compression Lug
Cable Size 2 AWG

G1 Lug 824-1

Type Compression Lug
Cable Size 2 AWG

Safety Features

Safety Features

The LayerZero eRDP-FSis designed for maximum operator safety. It uses a sectionalized design, which means that the power quality monitoring is housed in a separate section from the circuit breakers and customer cable connections. This compartmentalized design allows the equipment to be safely operated and serviced.

In normal operation, the inner dead-front doors of the HD2 remain closed.

A polycarbonate window in the door allows operators to safely view the circuit breaker positions with the dead front door closed. INSIGHT IR® cameras (optional) or an IR Port (standard) provides the ability to monitor the temperatures of critical connections with the doors safely closed.

The LayerZero Power Systems eRDP-FSis a safe and reliable piece of equipment that is designed to protect operators and equipment.

Reliability Features

Reliability Features

The LayerZero eRDP-FSis a highly reliable Remote Power Panel designed to provide power distribution and monitoring for critical applications. It offers advanced safety and reliability features to ensure consistent and dependable power delivery.

The eRDP-FSis built with high-quality components, ensuring long-lasting performance and reliability. HD2 features silver-plated connections, which enhance conductivity and minimize resistance, resulting in optimal power transmission.

With its comprehensive design, the eRDP-FSis capable of meeting the demands of various operating conditions. It incorporates a seismic rating, making it suitable for installations in seismically active areas. This ensures the stability and performance of the panel, even during earthquakes.

The eRDP-FSalso incorporates serialized board tracking, enabling easy identification and tracking of individual boards within the panel. This feature simplifies maintenance and troubleshooting, such as having the ability to detect for part defects.

With its reliable performance, advanced features, and safety-focused design, the LayerZero eRDP-FSis an excellent choice for organizations that require a dependable and safe remote power panel to support their critical applications.

Power Quality Monitoring Features

Power Quality Monitoring Features

The LayerZero eRDP-FSis equipped with an advanced Power Quality Monitoring (PQM) system that provides local and remote access using non-proprietary protocols. The PQM system includes basic monitoring, alarms, waveform capture, and ITIC plotting capabilities.

The ITIC plotting utility is used to audit the quality of transfers.

Connectivity Features

Connectivity Features
  • Ethernet Connectivity: This port is used to connect to to a network.
  • Modbus/TCP: This protocol is used to communicate with BMS systems.
  • SNMP Connectivity: This protocol is used to manage the switch remotely.

Where to Buy

Find Your Sales Rep

Find My Local Representative

*Select "Allow LayerZero.com To
Know Your Location" when prompted